Section 17 Trouble Shooting Flow Chart #1

Caution: Hazard of Electrical Shock

Symptoms:

Burner Will not attempt to fire. (Oil Primary Reset)


Is there line voltage (115 V)
in the heaters main electrical
junction box?

Yes

No

Call an Electrician.
Check main electrical

service and breaker.


Is the room thermostat
above

room

temperature?

No

Set room thermostat above

room temperature.



Yes



Remove room thermostat wires from
from oil primary control, install jumper
wire on T-T terminal, does the burner fire?

Yes

Is there an open circuit
in the thermostat wires?


No

No

Yes

Replace thermostat. Repair or replace thermostat wire.


Remove cad cell wires from
oil primary control, does
the burner fire?

No

Yes

Replace

cad

cell.

Page 36