Caution: hazard of electrical shock – Lanair HI140 User Manual
Page 56
Section 17 Trouble Shooting Flow Chart #3
Caution: Hazard of Electrical Shock
Symptoms:
1. Burner attempts to fire.
2. Poor flame.
3. No flame established.
4. Correct fuel output (see sec. 17, 17.1).
5. Oil Primary may lock out.
Note: Disable air operated fuel valve. Adjust burner air filter regulator to -0- PSI.
Look in inspection port at rear of burner.
Wear eye and face protection. Start
burner, do electrodes have spark? No
Are electrodes grounding out?
Yes
No
Remove electrodes
Is there voltage
clean or replace
(115V) to the ignition
see
sec.
16.5. transformer?
Yes
Yes
No
Replace the ignition
Check for loose
transformer.
wire
connections.
Is the combustion air blower working?
No
Is there voltage (115V) to the
combustion air blower motor?
Yes
Yes
No
Replace combustion
Check for loose
air blower motor.
wire connections.