LumaStream Trinity PERMANENT User Manual

Page 9

Advertising
background image

Document: 66APPMAN Rev: H

24 of 32

11.3 Analog Interface Specifications


The TRINITY ANALOG is compatible with commercial dimming panels and
wall box dimmer products meeting IEC 60929(AnnexE) requirements.

The TRINITY ANALOG has been tested with the following 0-10 Vdc Analog
wall box dimmer products:

·

HUNT PS LED series

·

LEVITON DECORA IP710_DL

Additional Analog 0-10 Vdc dimmer products may also be compatible with
the TRINITY ANALOG. Consult LumaStream for compatibility


11.4 Analog Interface Cabling and Connections


In the end use application, proper separation between the class 2 control
wiring from the analog 0-10 Vdc interface and AC mains must be
observed in accordance with the applicable safety standards and/or
NEC/CEC requirements.

The total run length of the 0-10Vdc control wiring (purple and grey) #18
AWG should not exceed 500 feet (150 meters). In situations where the
control wiring is greater than 500 feet or electrical noise is present,
shielded twisted pair cabling should be used.

CAUTION

RISK OF DAMAGE:

DO NOT connect AC input of power unit to a phase cut dimmer or dim-
ming panel It will cause internal damage to the power unit

Document: 66APPMAN Rev: H

9 of 32

5.0

INSTALLATION GUIDELINES AND SAFETY

REQUIREMENTS


This power unit has been evaluated to the requirements for:

UL 60950-1 2nd Edition - Information Technology Equipment-
Safety Part 1: General Requirements

CSA C22.2 No. 60950-1-03, 2nd Edition - Information Technology
Equipment-Safety Part 1: General Requirements

IEC 60950-1:2005 Second Edition

UL8750 1

st

Edition: LED Light Equipment for Use in Lighting Prod-

ucts

5.1 ELECTRICAL REQUIREMENTS

This power unit is intended for connection to a 20A branch circuit
and an appropriate disconnect device shall be provided as part of
the building installation.

All secondary output circuits are SELV, limited power source (LPS)
and Class 2.

5.2 MOUNTING AND ENVIRONMENTAL REQUIREMENTS

This power unit is limited to fixed plenum or non-plenum locations.
Only output cables marked with “CMP” may be installed in plenum
locations.

This power unit is rated for dry locations only.

The power unit is intended for use in a nonconductive pollution
environment only.

This power unit is rated for operation at a maximum ambient tem-
perature of 40 ºC.

Allow sufficient spacing around heatsink extrusion fins for convec-
tion air flow.

Do not block ventilation openings.

WARNING

RISK OF FIRE OR ELECTRIC SHOCK:

Shut OFF power at fuse box or circuit breaker before installation

Turn power OFF before inspection or removal

Properly ground power unit to main protective earthing

Follow all NEC/CEC, local electrical code requirements for installation

Do not remove enclosure cover. No serviceable parts inside

Do not connect Analog Interface to class 1 circuits

To reduce the risk of fire or electric shock, do not interconnect output
terminations