Figure 10

– Typical Dual Purpose Application w/ Wood Boiler

Figure 11

– Typical Dual Purpose Application

NOTES:

1. Minimum pipe size should match connection size. Upsize pipe accordingly if greater flow is required.
2. A thermal expansion tank suitable for potable water must be sized and installed within this piping system between the backflow preventer and the cold
water inlet.
3. All circulators should have an integral flow check.
4. Drains and check valve between unit and storage tank will assist in purging air from system.
5. This drawing is meant to demonstrate system piping only. The installer is responsible for all equipment and detailing required by local codes. In
Massachusetts, you must install a vacuum relief valve per 248 CMR.
6. Mixing valve application is optional, but recommended to help prevent scalding. See Part 3, Section E for more information.

7. On multiple source applications, use a Honeywell L4081-A-1148, which has (2) limit settings. This allows the wood stove to operate on the tank high
setting, and the tank low limit setting for conventional boiler back-up.