A. reduced boiler input sizing guide – HTP SuperStor Ultra Indirect Fired Water Heaters User Manual

Page 8

Advertising
background image

8

LP-83 Rev. 3.24.14

A. REDUCED BOILER INPUT SIZING GUIDE

NOTE: IT IS NOT RECOMMENDED TO REDUCE BOILER INPUT WHEN USING DOUBLE WALL TANKS.

MODEL

GROSS OUT

BTU/HR

GROSS OUT

BTU/HR

GROSS OUT

BTU/HR

GROSS OUT

BTU/HR

GROSS OUT

BTU/HR

GROSS OUT

BTU/HR

GROSS OUT

BTU/HR

199,000

220,000

240,000

260,000

280,000

300,000

320,000

A

370

370

370

-

-

-

-

SSU-60

B

266

266

266

-

-

-

-

A

489

503

503

503

503

503

-

SSU-80

B

359

370

370

-

370

370

-

A

457

470

543

627

645

645

645

SSU-119

B

335

345

399

460

474

474

474

Table 3

– DESCRIBES COLD START FIRST HOUR RATINGS (A and B) AND BOILER SIZE

PRODUCT LINE CONSISTS OF VARIOUS MODELS AVAILABLE IN DIFFERENT SIZES
CALL THE FACTORY FOR PRODUCT AND WARRANTY INFORMATION

“DW” (double wall heat exchanger) models are available in the 45, 60, 80, and 119 US gallon sizes.
“C” commercial models for dual systems or commercial applications; use one coil for wood boiler, the other for oil boiler; adaptable to solar systems as
well; good for hotels, motels, and apartments. Models are available in the 45, 60, 80, and 119 US gallon sizes.


DETERMINE AMOUNT OF DOMESTIC HOT WATER NEEDED. THEN USE THE CHART BELOW TO OPTIMIZE SUPERSTOR
ULTRA AND BOILER SIZING.

NOTE: FIRST DRAW AT 140

o

F at 90

o

F ΔT. (FOR PERFORMANCE AT 115

o

F, MULTIPLY BY 1.56 FOR MINUTES OF WATER DRAW.)

LINE A GALLONS - LOW MASS BOILERS THAT TAKE LESS THAN 90 SECONDS TO HEAT TO TEMPERATURE
LINE B GALLONS - HIGH MASS BOILERS THAT TAKE GREATER THAN 90 SECONDS TO HEAT TO TEMPERATURE

MODEL

2 GPM

2.5 GPM

3 GPM

3.5 GPM

4 GPM

4.5 GPM

5 GPM

A

9.5

8.0

7.0

5.5

4.5

4.0

3.5

SSU-20

B

8.5

7.5

6.5

5.0

4.0

3.5

3.0

A

16.0

13.0

10.0

7.5

6.0

5.5

5.0

SSU-30

B

14.0

12.0

9.0

7.0

5.5

5.0

4.5

A

18.0

14.0

12.0

9.0

6.5

6.0

5.5

SSU-30LB

B

17.0

12.0

10.0

8.0

6.0

5.5

5.0

A

23.0

18.0

14.0

11.0

8.5

7.5

7.0

SSU-45

B

18.0

15.0

13.0

10.0

7.5

7.5

6.5

A

29.0

20.0

17.0

14.0

SSU-45C

B

45.0

24.0

26.0

18.0

16.0

13.0

10.0

A

36.0

30.0

22.0

SSU-60

B

29.0

19.0

12.0

A

46.0

29.0

SSU-60C

B

30.0

21.0

A

SSU-80

B

A

SSU-80C

B

A

SSU-119

B

A

SSU-119C

B

Table 4 - NOTE: THIS INFORMATION IS BASED ON BOILER SIZE CONFORMING TO THE MINIMUM BTU/H REQUIRED TO
ACHIEVE FIRST HOUR RATINGS, OBTAINABLE FROM CHART ABOVE.
- Indicates infinity (continuous duty).