2 configuration using a gateway unit – IAI America ERC2 User Manual

Page 54

Advertising
background image



4. W

iring

35

4.2 Configuration Using a Gateway Unit

4.2.1 SIO Communication Connection Using a Relay Terminal Block

(Note 1) If the total length of the communication cable is 10 m or longer and you experience

communication errors, connect a terminal resistor to the last axis.

(Note 2) If the actuators use different power supplies, align 0 [V] on all power supplies.
(Note 3) The gateway unit power must be the same as 0 V of the ERC2 control power.
(Note 4) Connect the shielded wire of each axis to FG.
(Note 5) If the overall length of link cable exceeds 30 m, use wire of 22AWG or larger size.

PC software

RS232C type <RCM-101-MW>

USB type <RCM-101-USB>

Optional

Teaching

pendant

Relay terminal

block

Actuator 1

Actuator 2

Actuator 3

One-pair shielded cable

(Fabricated by the customer)

Terminal resistor

1/2W, 220 :

Actuator 16

Gateway

unit

J.S.T.

Mfg.

J.S.T.

Mfg.

24-VDC control power, motor power,

brake signal, ground, shield

Fabricated by the customer

Power & I/O cable