Chapter 3 Operation

POWER CON

PCON-CA/CFA

130

3.3.1 I/O Signal Controls

The input signals of this controller incorporate an input time constant to prevent malfunction

due to chattering, noise, etc. Make sure to input the signals continuously for 6ms or more.

(Note) Command pulse train inputs (PP•/PP, NP•/NP) do not have input time constants. Also, it

is necessary to input 16ms or more for CSTP Signal.

Caution: To use I/O signals, be sure to tilt the operation mode setting switch on the

front panel of the controller to the “AUTO” position.

3.3.2 Operation Ready and Auxiliary Signals

[1] System Ready (PWR)

Output

PIO signal

PWR

The signal is turned ON if the controller can be controlled after main power-on.

It is turned ON once the initialization terminates normally after main power-on and PCON can

be controlled regardless of alarm and servo status.

Even in the alarm condition, when the PCON can control the system, it is turned “ON”.

[2] Emergency stop status (*EMGS)

Output

PIO signal

*EMGS

1) The emergency stop status EMGS is turned ON when in normal condition and turned OFF

when EMG terminal on “2.1.3 [1] Power Supply Connector” is 0V (emergency stop

condition or disconnected).

2) It turns back ON once the emergency stop condition is released and EMG terminal goes

up to 24V DC. Have an appropriate safety treatment such as interlock with this signal for

the host controller (PLC, etc.).

Caution: It is not an emergency stop output due to an alarm generation of the

controller.

Identify

Does not identify

Input Signal

Input Signal

6ms