Chapter 9

Appendix

POWER CON

PCON-CA/CFA

224

[2] Wiring and setting of safety circuit

(1) Power supply

To use safety relays and/or contactors of 24V DC specification in the safety circuit, the

control power supply should be used only for the circuit as much as possible. (Do not use the

same power source as the driving power supply for this controller.)

It is the risk prevention treatment preparing for the cases such as the operation error of the

safety circuit caused by not enough power capacity.

(2) Specification of system I/O connector for TP adapter

Connector Name

System I/O Connector

Applicable Wire

Cable side

FMC1.5/6-ST-3.5

(Note 1)

Upper side

(EMG side) TP adapter side MCDN1.5/6-G1-3.5P26THR

Cable side

FMC1.5/6-ST-3.5

(Note 1)

Lower side

(ENB side) TP adapter side MCDN1.5/6-G1-3.5P26THR

Phoenix Contact AWG24 to 16

(0.2 to 1.25m

2

)

Pin No.

Signal

name

Description

1

EMG1-

2

EMG1+

Emergency stop contact 1

(30V DC or less, 100mA or less) 

3

EMG2-

4

EMG2+

Emergency stop contact 2

(30V DC or less, 100mA or less)

5

EMGIN

Emergency stop detection input

Upper side

(EMG side)

6

EMGOUT 24V power supply output for emergency stop

detection input

7

ENB1-

8

ENB1+

Enable contact 1

(30V DC or less, 100mA or less)

9

ENB2-

10

ENB2+

Enable contact 2

(30V DC or less, 100mA or less)

11

ENBIN

Enable detection input

Lower side

(ENB side)

12

ENBOUT 24V power supply output for enable detection

input

Note 1 Connectors on the cable side are attached under conditions where initial wiring has

been conducted.

In order to support each category, remove the initial wiring and wire your safety circuit.