Inverter Drive Error Codes

9001889

58

Stall prevention
(overcurrent)

During acceleration–If a current of more
than 150% of the rated inverter current
flows in the motor this function stops the
increase in frequency until the overload
current reduces to prevent the inverter
from resulting in overcurrent shut-off.
When the overload current has reduces
below 150%, this function increases the
frequency again.
During constant-speed operation–If a
current of more than 150%, this function
lowers the frequency again.
When the overload current has reduces
below 150%, this function increases the
frequency again.
During deceleration–If a current of more
than 150% of the rated inverter current
flows in the motor, this function stops the
decrease in frequency until the overload
current reduces to prevent the inverter
from resulting in overcurrent shut-off.
When the overload current has reduced
below 150%, this function decreases the
frequency again.

Check to make sure

the machine is
loaded properly and
that the load is

balanced.

Verify that the AC

drive’s parameters
are correct.

Load the machine

properly to
distribute the load
evenly.

Contact Alliance

Laundry Systems’

Customer Service
department.

Stall prevention
(overvoltage)

During deceleration-If the regenerative
energy of the motor exceeds the brake
capability, this function stops the decrease
in frequency to prevent overvoltage
shutoff. As soon as the regenerative
energy has reduced, deceleration resumes.

Check to make sure
the machine is loaded
properly and that the
load is balanced.

Load the machine
properly to distribute
the load evenly.

PU stop

A stop made by pressing the

key of

the PU has been set in Pr. 75 “PU stop
selection”.

Check for a stop made
by pressing the

key of the operation
panel during external
operation.

Perform operation
correctly.

This alarm appears if:

The RES signal is on;

You attempted to set any parameter

value in the external operation mode;

You attempted to change the operation

mode during operation;

You attempted to set any parameter

value outside its setting range.

You attempted to set any parameter

value during operation (while signal

STF or STR is ON).

You attempted to set any parameter

value while parameter write is being
inhibited in Pr. 77 “parameter write
inhibit selection”.

Perform operation
correctly.

Operation

Panel

Indication

Name

Description and NOTES

Check point

Corrective action

STOP

RESET

STOP

RESET