Specifications

Ethernet

Comments

802.3 Compliant

Yes

Speed

10/100 Mbit

Auto MDI-X

Yes

Crossover cable not required

OUI

00-26-c8

MAC addresses: 00-26-c8-xx-xx-xx

TCP/IP

Version

IPv4

DHCP

Optional

DHCP Retry Period

5 x 50 seconds

DNS Name Resolution

Yes

NetBIOS Name Resolution

Yes

When receiving its IP address via DHCP, the detector will register its name

with a NetBIOS network and be accessible by its hostname.

Automatic Private IP Addressing

Yes

IP Address (default)

192.168.1.10

Subnet Mask (default)

255.255.255.0

PC (PipeIQ) Server

TCP Port

1937

Password Protected

Yes

Administrator password required to change configuration; not required for

monitoring

Administrator Password (default)

password

Configuration Changes

Yes

Live View Refresh Period

15 seconds

Minimum Trend Graph Update Period

5 seconds

Maximum Simultaneous Connections

1

Web Server

TCP port

80

Password Protected

Yes

Web-Access password required for monitoring

Web Access Password (default)

1234

Configuration Changes

No

Automatic Logoff Period

60 minutes

Live View Refresh Period

10 seconds

Maximum Simultaneous Connections

2

SMTP E-mail Client

TCP port

25

Initialization Time

5 minutes

SSL/TLS

No

Password Authentication

No

Maximum SMTP Server Name Length

48 characters

Maximum E-mail Address Length

48 characters