Vanguard VCBA S2 (DigiTMR S2, DigiTMR S2 PC, CT-6500 S2, CT-7000 S2, CT-7500 S2, CT-8000) User Manual

Page 80

Advertising
background image

VCBA S2 VERSION 4.xx SOFTWARE MANUAL

REV 3

77

6. From the “Timing Window” radio box group, select “1 second”. The 1 second timing

window should always be used since it provides the required adequate resolution (±50
micro-seconds) for dynamic tests.

7. From the “Insertion Resistor” radio box group, select the desired insertion resistance

value.

8. Check the “Dynamic Resistance” checkbox.

9. From the “Trigger Type” radio box group, select the trigger type.

10. Click on the “OK” button. The following window will be displayed:

11. A 5-second timer will count down, and then the test will be initiated. A sequence of

status messages will be displayed. When the test is complete, the data will be
transferred from the CB analyzer to the PC. When the data has been transferred to the
PC, the results will be displayed in the VCBA S2 software. The test record will also be
saved in the location selected in step 4.















Advertising