ENTER READING CONFIGURATION MENU:

Press

a

1) Press

a, if necessary, until CNFG prompt appears.

Press

d

2) Display advances to

INPT Input Menu.

Press

a

3) Display advances to

RDG Reading Configuration Menu.

Press

d

4) Display advances to

DEC Decimal Point.

DECIMAL POINT SUBMENU:

Press

d

5) Display flashes previous selection for Decimal location.

Press

b

6) Scroll though the available selections and choose Decimal
location:

FFFF or FFF.F (also FF.FF and F.FFF — if PROC

Process type was selected in the Input Type Menu).

Press

d

7) Display shows

STRD stored message momentarily and then

advances to

TEMP Temperature Unit.

Decimal Point for Process Input Type is passive.

TEMPERATURE UNIT SUBMENU:

Press

d

8) Display flashes previous Temperature Unit selection.

Press

b

9) Scroll though the available selections to the Temperature Unit
of your choice:

°F or °C.

Press

d

10) Display shows

STRD stored message momentarily and then

advances to

FLTR Filter Constant.

FILTER CONSTANT SUBMENU:

Press

d

11) Display flashes previous selection for Filter Constant.

Press

b

12) Scroll though the available selections:

0001, 0002, 0004,

0008, 0016, 0032, 0064, 0128. - Default is 0004

Press

d

13) Display shows

STRD stored message momentarily only, if a

change was made, otherwise press

a to advance to the next menu.

If Process was selected in the Input Type Menu the display will
advance to

IN.RD Input/Reading Submenu, otherwise the

display advances to the

ALR1 Alarm 1 Menu.

The Filter Constant Submenu allows the user to specify the
number of readings stored in the Digital Averaging Filter.

For PID control select filter value 0001-0004. A filter value of 2 is
approximately equal to 1 second RC low pass time constant.