CONTACT CLOSURE SUBMENU:

Press

d

11) Display flashes previous selection. Press

b to N.ç. Normally

Closed or

N.o. Normally Open.

Press

d

12) Display shows

STRD stored message momentarily and then

advances to

AçTV only, if it was changed, otherwise press a to

advance to

AçTV Active Submenu.

Normally Open: If this feature is selected, then the relay is "energized" only
when an alarm condition occurs.

Normally Closed: "Fail Safe" Mode. Relay is energized under "normal"
conditions and becomes de-energized during alarm or power failure.

ACTIVE SUBMENU:

Press

d

13) Display flashes previous selection. Press

b to scroll through

the available selections:

ABoV Above, BELo Below, HI.Lo

HI/Low and

BAND Band. (Band is active if _DEV Deviation was

selected).

Press

d

14) Display shows

STRD stored message momentarily and then

advances to

A.P.oN only, if it was changed, otherwise press a to

advance to

A.P.oN Alarm Enable/Disable at Power On Submenu.

Above: Alarm 1 condition triggered when the process variable is greater than the
Alarm Hi Value (Low value ignored).
Below: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).
Hi/Low: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.
Band: Alarm 1 condition triggered when the process variable is above or below
the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.
The Band for the AL 1 would be following the Setpoint 1 value
The Band for the AL 2 would be following the Setpoint 2 value.
The Band or the Deviation Value should be entered under:

AL1 High (if they want Alarm 1)
AL2 High (if they want Alarm 2)
AL Low value is ignored in the Band mode.

Example: if customer requires a Deviation Value of ±10 degrees around a
setpoint (using Output 2 as alarm)

Alarm 2: - Deviation
Contact Closure type: Deviation---Band
AL2 High: 10 (Band they want around Setpoint 2)

Then the Band Value is to be entered under AL2 HI: 10 not 80+10 = 90