NEWPORT iDRA Controller User Manual

Page 59

Advertising
background image

55

ALARM 1 & 2(programmable):
Type
Same as Output 1 & 2

Operation High/low, above/below,
band, latch/unlatch, normally
open/normally closed and
process/deviation; front panel
configurations

OUTPUT 3
ANALOG OUTPUT (programmable)
Isolated, Retransmission 0 to 10 Vdc or
0 to 20 mA, 500 Ω max.
Accuracy is 1% of FS,
for Scaling Gain from
0.03 to 100 mV per count
Isolation is 1000 Vdc
Linearity is 0.2%

COMMUNICATIONS
(Optional in place of excitation)

RS-232/RS-422/RS-485/MODBUS:
Selectable from menu; both ASCII and
modbus protocol selectable from menu.
Programmable 300 to 19.2 K baud;
complete programmable setup
capability; program to transmit current
display, alarm status, min/max, actual
measured input value and status.

RS-485 Addressable from 0 to 199

CONTROL
Action: Reverse (heat) or direct (cool)
Modes
Time and Amplitude Proportional
Control Modes; selectable Manual or
Auto PID, Proportional, Proportional
with Integral, Proportional with
Derivative with Anti-reset Windup and
ON/OFF

Rate
0 to 399.9 seconds

Reset
0 to 3999 seconds

Cycle Time
1 to 199 seconds; set to 0 for ON/OFF
operation

Gain
0.5 to 100% of span; Setpoints 1 or 2

Damping
0000 to 0008

Soak
00.00 to 99.59 (HH:MM), or OFF

Ramp to Setpoint
00.00 to 99.59 (HH:MM), or OFF

Auto Tune
Operator initiated from front panel

CONTROL OUTPUT 1
Configurable as Alarm 1, On/Off, PID
and Ramp and Soak

Relay
SPDT type, 250 Vac or 30 Vac @ 3 A
(Resistive Load);

SSR
20-265 Vac @ 0.05-0.5 A
(Resistive Load); continuous

DC Pulse
Non-Isolated; 10 Vdc @ 20 mA

Advertising