2 wiring to the dio connector, 2 wiring to the dio connector -6, 6 5.2 wiring to the dio connector – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 159

Advertising
background image

GP3000 Series Hardware Manual

5-6

5.2

Wiring to the DIO Connector

‹ Items Required to Wire Connectors

Screwdriver

Recommended type: 1891348-1 <Tyco Electronics AMP.>

If another manufacturer is used, be sure the part has the following dimensions:

point depth: 1.5mm [0.06in.]

point width: 2.4mm [0.09in.]

Point shape should be DIN5264A, and meet Security Standard DN EN60900.

Also, the screwdriver’s tip should be flat as indicated in order to access the narrow hole of the connector:

The connectors are a spring clamp type.

Use the following procedure to connect the wires to the connectors.

„ DIO Cable Specifications

„ Connecting the DIO Cable

(1)

Insert a slot screwdriver, at an angle, into the tool insertion hole (square-shaped hole) of the connector.

(2)

When inserting the flathead screw driver, be sure that it is perpendicular to the center division wall.

Be sure to remove the DIO Connector from the GP unit prior to starting wiring. Failure to do

so may cause an electric shock.

DIO Cable Diameter

AWG24 to 18
UL1015 or UL1007

Conductor Type

Stranded Wire

*1

*1 If the Conductor’s end (individual) wires are not twisted correctly, the end

wires may either short against each other, or against an electrode.

Conductor Length

Insert the screwdriver approximately 4 mm [0.16 in.]. Inserting forcefully may break the inside

of the connector and cause a contact defect.

Also, do not turn the screwdriver while the tip is inside of the tool insertion hole (square-shaped

hole).

Screwdriver Tip
Shape

7 mm
[0.28in]

Advertising