GP3000 Series Hardware Manual

6-4

6.2.2

Wiring to the FLEX NETWORK Connector

Remove the wire’s external covering and insert the wire center strand into the opening.

The applicable wire size is AWG28-16. Strip at least 7.0mm [0.28in.] of cover from the wire.

Be sure to remove the FLEX NETWORK Connector from the GP unit prior to starting wir-

ing. Failure to do so may cause an electric shock.

• Tightening torque is 0.25N

•m.

• Be sure to tape or put a plastic tube over the shield line.

• Do not solder the wire itself. This could lead to a bad or poor contact.

Use a small sized screwdriver to tighten the set screws. (Point depth: 0.6mm [0.02in.], point

height: 2.5mm [0.10in.])

If the central wire’s end (individual) wires are not twisted correctly, the end wires may either

short against each other, or against an electrode. To use a pin terminal, reference the recom-

mended pin terminal shown below or equivalent terminals. The optimum pin terminal varies

depending on the size of the electric wire to be used.

-966067-

manufactured by Tyco Electronics AMP.

Blue (TR+)

6 to 7 [0.24 to 0.28]

White (TR-)

25 to 35
[0.98 to 1.38]

Shield (SLD)

* Do not solder end

Unit: mm[in.]