4 wiring precautions, 4 wiring precautions -14 – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 185

Advertising
background image

GP3000 Series Hardware Manual

8-14

8.2.4

Wiring Precautions

To help prevent noise and interference problems, separate all control, communication and power lines by

placing them in a separate ducts.

If different wires must be placed in the same duct, separate them with an earthed/grounded divider.

If the lines cannot be separated, use shielded lines and create a ground from the shield line.

• Use noise-reducing external wiring methods to increase overall system reliability.

• To prevent power surges or noise interference, use ducts to separate all DC I/O

or current circuit wires from communication cables.

• To prevent malfunctions due to noise, communication cables must be wired

separately from high-frequency lines and power lines such as high-voltage lines,

high-current lines, and inverters.

Duct for I/O Signal

Lines

Duct for Control

Lines

Duct for Power

Lines

I/O Signal Lines

Control Lines

Power Lines

Grounded

Separators

Duct
(non-conducting
resin/plastic)

Earth/Ground

Advertising