General Specifications
Electrical Specifications
Environmental Specifications
Power Supply
Input Voltage
DC24V
Rated Voltage
DC19.2 to 28.8V
Allowable Voltage Drop
2ms (max.)
Power Consumption
13W (max.)
In-Rush Current
60A (max.)
*1
*1
Half width (Time duration with a current exceeding 30A): 40
µs max.
Voltage Endurance
AC1000V 20mA for 1 minute
(between charging and FG terminals)
Insulation Resistance
DC500V 10M
Ω (min.)
(between charging and FG terminals)
Physical
Surrounding Air
Temperature
0 to 50°C
*1
*1
In the case of AGP-3200A, Extended use in environments where Surrounding air temperature is 40°C or
higher may degrade the display quality and result in decreased contrast.
Storage Temperature
-20 to +60°C
Ambient Humidity
10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)
Storage Humidity
10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)
Dust
0.1mg/m
3
and below (non-conductive levels)
Pollution Degree
For use in Pollution Degree 2 environment
Atmosphere
Free of corrosive gases
Air Pressure Vibration
Resistance (altitude
range)
800 to 1114hPa
(2,000 meters above sea-level and below)
Mechanical
Vibration Resistance
IEC61131-2 compliant
5 to 9Hz single-amplitude 3.5mm
9 to 150Hz constant-accelerated velocity 9.8m/s
2
X,Y,Z directions for 10 cycle (100 minute)
Concussion Resistance
IEC61131-2 compliant
(147m/s
2
X,Y,Z directions for 3 time)
Electrical
Noise Immunity
Noise Voltage: 1000V
P-P
Pulse Duration: 1
µs
Rise Time: 1ns
(via noise simulator)
Electrostatic Discharge
Immunity
6kV (complies with EN 61000-4-2 Level 3)