LT-4201TM/4301TM Installation Guide

41

English

Common Grounding

If exclusive grounding is not possible, use a common grounding point. Use grounding
resistance of 10

Ω or less, wire thickness of 2.6 mm or more, or your country’s applicable

standard for the grounding point.

Precautions:

Do not use common grounding, since it can lead to accidents and machine breakdown.

If the equipment does not function properly when grounded, disconnect the ground wire
from the FG terminal.

If exclusive grounding is not possible, use a common connection point.

Grounding Procedure

NOTE: FG and SG terminals are internally connected in the LT. When connecting an
external device to the LT using the SG terminal, be sure to check that no short-circuit loop
is created when you setup the system.

Step

Action

1

Check that the grounding resistance is less than 100

Ω.

(Grounding resistance of 100

Ω or less, wire thickness of 1.6 mm or more, or your

country’s applicable standard.)

2

Create the connection point as close to the unit as possible, and make the wire as short
as possible. When using a long grounding wire, replace the thin wire with a thicker wire,
and place it in a duct.