Sensor Installation Guidelines

We suggest you mount the sensor at a location in your process or system where
it reads an average temperature. Put the sensor as near as possible to the mate-
rial or space you want to protect. Air flow past this sensor should be moderate.
The sensor should be thermally insulated from the sensor mounting.

See Chapter 4 for more information on DIP switch location and orientation.

Input Wiring

Figure 2.4a –

Thermocouple

Extension wire for thermocouples must be of the same alloy as the thermo-
couple itself to limit errors.

DIP Switch orientation

Figure 2.4b –

RTD (2- or 3-Wire) 100

Platinum

There could be a + 2°F input error for every 1

of lead length resistance

when using a 2-wire RTD. That resistance, when added to the RTD element
resistance, will result in erroneous input to the instrument. To overcome
this problem, use a 3-wire RTD sensor, which compensates for lead length
resistance. When extension wire is used for a 3-wire RTD, all wires must
have the same electrical resistance (i.e. same gauge, same length, multi-
stranded or solid, same metal).

DIP Switch orientation

O
N

1

2

S1

S2

S3

2

3

5

3-wire RTD

S1

S2

S3

2

3

5

2-wire RTD

Jumper

Terminals

3 and 5.

O
N

1

2

T/C

+

3

-

5

Install and Wire

2 . 4

I n s t a l l a n d W i r e

W a t l o w S e r i e s 9 4

Ó

WARNING: To avoid elec-
tric shock and damage to
property and equipment,
use National Electric
Code (NEC) safety prac-
tices when wiring and
connecting this unit to a
power source and to elec-
trical sensors or peripher-
al devices. Failure to do
so could result in injury or
death.