Output wiring, Output 1 wiring, Output 2 wiring – Watlow Series 94 User Manual

Page 11: Mechanical relay without contact suppression, Install and wire

Advertising
background image

W a t l o w S e r i e s 9 4

I n s t a l l a n d W i r e

2 . 5

Output 1 Wiring

Figure 2.5a

– Mechanical Relay Without Contact Suppression

94_ _- 1D _ _- 00 _ _

Form C, 5 amps

Minimum load current:

100 mA at 5VÎ (dc)

Output 2 Wiring

Figure 2.5b

– Mechanical Relay Without Contact Suppression

94_ _- 1D D _ - 00_ _

Form C, 5 Amp

Minimum load current:

100 mA at 5VÎ (dc)

6 COM

NC 1

7 NO

Customer installed

Quencharc for inductive

loads only. See note 1.

L1

L2

Customer installed

Quencharc for inductive

loads only. See note 1.

Install and Wire

NOTE:

Successful installa-
tion requires four
steps:

• Choose the con-
troller’s hardware
configuration and
model number
(Appendix);

• Choose a sensor
(Chapter Two and
Appendix);

• Install and wire the
controller (Chapter
Two);

• Configure the con-

troller (Chapters
Three, Four and
Five).

NOTE 1:

Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical relay,
switched dc or solid-
state relay output
options requires use
of an R.C. suppressor.

Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow Part
No. 0804-0147-0000.

Ó

WARNING: To avoid
damage to property
and equipment,
and/or injury or loss
of life, use National
Electric Code (NEC)
standard wiring prac-
tices to install and
operate the Series
94. Failure to do so
could result in such
damage, and/or
injury or death.

N.O. contact opens in limit condition.
N.C. contact closes in limit condition.

N.O. contact opens in alarm condition.
N.C. contact closes in alarm condition.