Wiring example, Install and wire, Figure 2.7 - system wiring example – Watlow Series 94 User Manual

Page 13

Advertising
background image

W a t l o w S e r i e s 9 4

I n s t a l l a n d W i r e

2 . 7

Wiring Example

Figure 2.7 - System wiring example.

1

120Å (ac)

L1

L2

2

3

5

4

5

1

2

1

(+)

(-)

3

12

13

14

2

1CR

15

1

2

3

4

7

8

9

10

11

11

3

5


DIN-a-mite
DA10-24C0-0000

16

1

8

Heater

2

6

1

5

1 CR-1

9

2

9

10

(+)

(-)

12

5

6

Limit Controller

Series 93

93BB-1CA0-00RR

Temperature Controller

Series 94

94BB-1DA0-00RR

12

9

12

10

8

3

4

6

7

10

11

11

94AA-1DA0-00RR

1 Not used
2 S1
3 S2, TC+
4 Not used
5 S3, TC-
6 not used
7 not used
8 N.C.1
9 COM.1
10 N.O.1
11 L1
12 L2

5 -

DIN-a-mite

DA10-24C0-0000

1

Coil

9 (+)

10 (-)

High Limit

Mechanical

Controller

Heater

94BB-1DA0-00RR

Limit Controller

Limit Sensor

Process Sensor

93BB-1CA0-00RR

Rear View

5 (-)

3 (+)

11 12

Fuse

Earth Ground

L1

L2

120VÅ (ac)

11 12

9

3 +

10

2

3

4

6 (-)

5 (+)

Install and Wire

NOTE:

Successful installation
requires four steps:

• Choose the controller’s
hardware configuration
and model number
(Appendix);

• Choose a sensor
(Chapter Two and
Appendix);

• Install and wire the
controller (Chapter Two);

• Configure the con-

troller (Chapters Three,
Four and Five).

NOTE 3:

Output is in open state in
Alarm Condition.

NOTE 1:

Switching inductive loads
(relay coils, solenoids,
etc.) with the mechanical
relay, solid-state relay
output options requires
use of an R.C. suppres-
sor.

Watlow carries the R.C.
suppressor Quencharc
brand name, which is a
trademark of ITW Paktron.
Watlow Part No. 0804-
0147-0000.

Ó

WARNING: To avoid dam-
age to property and equip-
ment, and/or injury or
loss of life, use National
Electric Code (NEC) stan-
dard wiring practices to
install and operate the
Series 94. Failure to do
so could result in such
damage, and/or injury or
death.

See note 3.