<5. Parameter Setting>

5-4

IM 01C25T04-01EN

a. Auto Adjustment

Applying reference pressure of 0% and 100% of the

measurement range to the transmitter, adjust the

lower and upper points automatically.

• Procedure to call up the display

DTM

Calibration → Pressure

Calibration → Calibration →

EDD

[Menu] → Device → Sensor

Calibration → Pressure

Calibration → Calibration →

→ Lower Calibration

Point

Auto adjustment for 0% point

→ Upper Calibration

Point

Auto adjustment for 100% point

b. Manual Adjustment

Using the example below, follow the steps to

perform the full sensor trim by manually. Suppose

that Lower Calibration Deviation and Upper

Calibration Deviation represent the previously

adjusted values.

Example: For the range of 1000 to 3000 mmH

2

O

Lower Calibration Deviation: −4.0 mmH

2

O

Upper Calibration Deviation: −3.0 mmH

2

O

<1> Call up the Lower Calibration Deviation

• Procedure to call up the display

DTM

Calibration → Pressure

Calibration → Calibration →

EDD

[Menu] → Device → Sensor

Calibration → Pressure

Calibration → Calibration →

→ Lower Calibration

Deviation

Adjust the lower point

<2> Suppose that a standard pressure of 1000

mmH

2

O is applied and the value of the output

signal is 994 mmH

2

O. Correct for this output

error of 6 mmH

2

O by adding 6 mmH

2

O to

Lower Calibration Deviation.

−4.0+6.0=+2.0

<3> Enter the correction value of “2” to the Lower

Calibration Deviation.

<4> Call up the Upper Calibration Deviation

• Procedure to call up the display

DTM

Calibration → Pressure

Calibration → Calibration →

EDD

[Menu] → Device → Sensor

Calibration → Pressure

Calibration → Calibration →

→ Upper Calibration

Deviation

Adjust the upper point

<5> Suppose that a standard pressure of 3000

mmH

2

O is applied and the value of the output

is 3015.0. Firstly, obtain the slope error for the

span as follows.
Slope Error=

3000−3015/3000×(3000-1000)=−10

Then correct this slope error of −10 by adding

−10 to Upper Calibration Deviation.

−3.0+(−10)=−13

<6> Enter the correction value of “-13” to the Upper

Calibration Deviation.

(3) Static Pressure Calibration
For the transmitter, full sensor calibration of the

static pressure is performed in the same way as

with the differential pressure.

• Procedure to call up the display

DTM

Calibration → Static Pressure

Calibration → Calibration →

EDD

[Menu] → Device → Sensor

Calibration → Static Pressure

Calibration → Calibration →

→ SP Lower

Calibration Point

Auto adjustment for 0% point

→ SP Upper

Calibration Point

Auto adjustment for 100% point

→ SP Lower

Calibration

Deviation

Manual adjustment for 0% point

→ SP Upper

Calibration

Deviation

Manual adjustment for 100%

point