<8. Diagnostic Information>

8-8

IM 01C25T04-01EN

Table 8.5

Action of each parameters in failure mode related Sensor Transducer block (Classic status)

ALARM

Display

Cause of

Alarm

SENSOR Transducer block

NAMUR

NE107

Category

Pressure Value

Primary Value

Calculated Value

Static Pressure Value Capsule Temp

Amplifier Temperature

Value

Status

Value

Status

Value

Status

Value

Status

AL.01

CAP.

ERR

Pressure

Sensor

problem

Measured

Value

BAD: Sensor

Failure

Measured

Value

BAD: Sensor

Failure

Measured

Value

BAD: Sensor

Failure

Measured

Value

BAD: Sensor

Failure

F

Capsule

Temperature

Sensor

problem
Capsule

memory

problem

Hold

Value

BAD: device

failure

Hold

Value

BAD: device

failure

BAD: device

failure

BAD: device

failure

AL.02

AMP.

ERR

Amplifier

Temperature

Sensor

problem

Measured

Value

BAD: Sensor

Failure

Measured

Value

BAD: Sensor

Failure

BAD: Sensor

Failure

BAD: Sensor

Failure

Amplifier

memory

problem

Hold

Value

BAD: device

failure

Hold

Value

BAD: device

failure

BAD: device

failure

Hold

Value

BAD: device

failure

Amplifier

problem

AL.10

PRESS

Input Pressure

is outside

measurement

range limit of

capsule"

Measured

Value

UNCERTAIN:

sensor

conversion

not accurate

Measured

Value

UNCERTAIN:

sub normal

Measured

Value

GOOD (NC):

OK

Measured

Value

GOOD (NC):

OK

S

AL.11

ST.PRSS

Static

Pressure

exceeds limit

UNCERTAIN:

sub normal

UNCERTAIN:

sensor

conversion

not accurate

AL.12

CAP.

TMP

Capsule

Temerature is

out of range

UNCERTAIN:

sub normal

UNCERTAIN:

sensor

conversion

not accurate

AL.13

AMP.

TMP

Amplifier

Temperature

is out of range

GOOD (NC):

OK

GOOD (NC):

OK

GOOD (NC):

OK

UNCERTAIN:

sensor

conversion

not accurate

AL.30

HI.HI

LO.LO

Hi_Hi or

Lo_Lo Alarm

occurs in AI1

Function block

Measured

Value

GOOD (NC):

OK

Measured

Value

GOOD (NC):

OK

Measured

Value

GOOD (NC):

OK

Measured

Value

GOOD (NC):

OK

---

AL.31

HI.HI

LO.LO

Hi_Hi or

Lo_Lo Alarm

occurs in AI2

Function block

AL.32

HI.HI

LO.LO

Hi_Hi or

Lo_Lo Alarm

occurs in AI3

Function block

AL.33

HI.HI

LO.LO

Hi_Hi or

Lo_Lo Alarm

occurs in

Totalizer

Function block