Yokogawa EJX115A User Manual

Page 56

Advertising
background image

<8. Diagnostic Information>

8-10

IM 01C25T04-01EN

Table 8.6

Action of each parameters in failure mode related Function blocks (Condensed status)

ALARM

Display

Cause of

Alarm

AI1 Output Value (Channel = Primary Value)

Totalizer Value (Channel = Calculate Value) NAMUR

NE107

Category

FSAFE_TYPE

= 0

FSAFE_TYPE

= 1

FSAFE_TYPE

= 2

FSAFE_TYPE

= 0

FSAFE_TYPE

= 1

FSAFE_TYPE

= 2

AL.01

CAP.

ERR

Pressure

Sensor

problem

UNCERTAIN:

Substitute Set

UNCERTAIN:

Substitute Set

BAD:

Maintenance

Alarm, more

diagnosis

available

BAD:

Maintenance

Alarm, more

diagnosis

available ok

limit

BAD:

Maintenance

Alarm, more

diagnosis

available Const

limit

UNCERTAIN:

Substitute Set

ok limit

F

Capsule

Temperature

Sensor

problem
Capsule

memory

problem

AL.02

AMP.

ERR

Amplifier

Temperature

Sensor

problem
Amplifier

memory

problem
Amplifier

problem

AL.10

PRESS

Input Pressure

is outside

measurement

range limit of

capsule

UNCERTAIN:

Process

related, no

maintenance

UNCERTAIN:

Process

related, no

maintenance

UNCERTAIN:

Process

related, no

maintenance

UNCERTAIN:

Process

related, no

maintenance

UNCERTAIN:

Process

related, no

maintenance

UNCERTAIN:

Process

related, no

maintenance

S

AL.11

ST.PRSS

Static Pressure

exceeds limit

AL.12

CAP.

TMP

Capsule

Temerature is

out of range

AL.13

AMP.

TMP

Amplifier

Temperature is

out of range

GOOD (NC):

OK

GOOD (NC):

OK

GOOD (NC):

OK

GOOD (NC):

OK

GOOD (NC):

OK

GOOD (NC):

OK

AL.30

HI.HI

LO.LO

Hi_Hi or Lo_Lo

Alarm occurs

in AI1 Function

block

GOOD(NC):

Active Critical

Alarm High

limited or Low

Limited

GOOD(NC):

Active Critical

Alarm High

limited or Low

Limited

GOOD(NC):

Active Critical

Alarm High

limited or Low

Limited

GOOD (NC):

OK

GOOD (NC):

OK

GOOD (NC):

OK

---

AL.31

HI.HI

LO.LO

Hi_Hi or Lo_Lo

Alarm occurs

in AI2 Function

block

GOOD (NC):

OK

GOOD (NC):

OK

GOOD (NC):

OK

AL.32

HI.HI

LO.LO

Hi_Hi or Lo_Lo

Alarm occurs

in AI3 Function

block

AL.33

HI.HI

LO.LO

Hi_Hi or Lo_Lo

Alarm occurs

in Totalizer

Function block

GOOD(NC):

Active Critical

Alarm High

limited or Low

Limited

GOOD(NC):

Active Critical

Alarm High

limited or Low

Limited

GOOD(NC):

Active Critical

Alarm High

limited or Low

Limited

Advertising