<6 OPERATION>

6-29

IM 01R01A11-01EN

(A) Pulse Output (without optional code EM)

1) Wire AXF and CA150 Handy Calibrator or similar as shown in

Figure 6.3.9.

2) Select “100 pps” in “Setting Value”. See

Figure 6.3.7.

F060307.ai

Figure 6.3.7 “Setting Value” in “Pulse Output”

3) Output

3)-1 When Verifi cation Tool is in “online” mode:

Select “Pulse” in “Output Selection” and click “Output”. See

Figure 6.3.8

F060308.ai

Figure 6.3.8 “Output Selection” in “Pulse Output”

3)-2 When Verifi cation Tool is in “offl ine” mode:

3)-2-1 Record the original AXF parameters, and then set them as shown below.

Table 6.3.5 Parameter Settings of “Pulse Output”

HART Parameter

Parameter of

AXF Display

Setting Value

Pulse Scale

Device Setup → Easy Setup → Pulse Scale

B33/E11

100

Pulse Width

Device Setup → Pulse Set → Pulse Width

E12

50% Duty

Pulse Unit

Device Setup → Easy Setup → Pulse Scale

B32/E10

Pulse/s

Test DO (*1)

Device Setup → Diag/Service → Output Test→ Test DO

N30

Pulse

DO Function(*1) Device Setup → Confi guration → Status Function

→ DO Function

F20

Pulse Output

*1: Only for AXFA14 or AXF Integral Flowmeter

3)-2-2 Output pulse by setting AXF HART parameter “Loop test” to “20 mA”.

Table 6.3.6 Parameter Setting of “Pulse Output”

HART Parameter (DD)

Parameter of

AXF Display

Setting Value

Loop test

Device Setup → Diag/Service → Output Test→ Loop test

-

20 mA