6 operation, A) axfa11, Figure 6.3.10 “pulse output” result – Yokogawa FieldMate User Manual

Page 62

Advertising
background image

<6 OPERATION>

6-30

IM 01R01A11-01EN

NOTE

■ Measure for more than 60 seconds.
■ If using a YOKOGAWA CA150, set the mode to “Contact Input” and the range to “CPM”.

4) Measure the pulse output value in “pps” with a Yokogawa CA150 Handy Calibrator or

equivalent to simplify the measurement of pulses. If such a device is unavailable, an appro-

priate load (30V DC, 0.2A max) is required and use the confi guration shown in

Figure 6.3.9.

SB

B

A

SA

C

AL–

AL+

COM

SO2+

SO1+

I+

I–

CUR OUT

STATUS OUT

ALARM OUT

SIGNAL

COM

SI2+

SI1+

EX2

EX1

L/+

N/–

POWER SUPPLY

EXCITER

P–

P+

PULSE OUT

STATUS IN

Electronic Counter

30VDC , 0.2A. max

External

power supply

Load

Dashed box : Yokogawa CA150 Handy Calibrator or equivalent

F060309-A.ai

(A) AXFA11

Electronic Counter

30VDC , 0.2A. max

External

power supply

Load

Dashed box : Yokogawa CA150 Handy Calibrator or equivalent

F060309-B.ai

(B) AXFA14 or AXF Integral Flowmeter

Figure 6.3.9 Pulse Output Diagram (without optional code EM)

5) Enter the measured value manually.
6) “Result” is displayed automatically.

F060310.ai

Figure 6.3.10 “Pulse Output” Result