Linearize (when the pv/sp math function is off), Lnearze (when the pv/sp math functon s off) – Yokogawa DAQWORX User Manual

Page 279

Advertising
background image

8-22

IM WX104-01E

Reference Deviation

Turn the reference deviation on or off, and specify the value with the measurement

input span one-digit EUS (100.0%). It is not displayed when the PID number is 2 or

less.

Lnearze (When the PV/SP Math Functon s OFF)

Mode

Select the linearize mode from [OFF], [Biasing], or [Approximation].

Input

Enter the linearize input value. (The value depends on the linearize mode.)

Biasing: Set with the measurement input span EU (–5.0 to 105.0%).

Approximation: Set with the measurement input span EU (–5.0 to 105.0%).

You must set between 2 and 11 points total.

Output

Enter the linearize output value. (The value depends on the linearize mode.)

Biasing:

Set with measurement input span EUS (–100.0 to 100.0%).

Approximation: Set with measurement input span EU (–5.0 to 105.0%).

Note

• For biasing, set the values so that input + output is EU (0 to 100%). In addition, set the

values so that input + output is greater than or equal to the previous input + output.

• Set the approximation output to be greater than or equal to the previous value.

• If a value smaller than the previous value is specified for the third point or later, the settings

after that point are invalid.

• When the PV/SP math function is ON, the settings above are entered using [Control input

channel] items under the [Setting] tab for each control input channel. For the setting

procedure, see page 8-27.

8.4 Control Functon General Settngs