8.7

Basc Measurement Functon Settngs

To enter basic measurement function settings, click the [Setup] tab. Or, you can select

the items by choosing [Setting] - [SETUP [Basic] Setting] - [Setting].

Alarm/Relay/Remote

2. Click here. (Or choose the [Setting] menu - [SETUP [Basic] Setting] - [Setting].)

1. Select this tab.

Select the controlled item.

Select between

1 and 15.

Copy/Paste the

selected range.

Alarm/Relay

Select the alarm format. The selected items are blue.

Reflash

Set whether to use the alarm relay output reflash.

• Relay AND
Set the range of relays (from the first alarm relay) using the AND logic gate. All other

relays are set to the OR logic gate. If [NONE] is selected, all relays use the OR logic

gate.

• Relay Action

Select whether the alarm output relay should be [Energize] or [De-Energize] when an

alarm occurs.

• Alarm Relay Behavior

Select the output relay when returning from an alarm to the normal state of operation

(when the alarm is released). This applies to all alarm output relays. If the measuring

alarm output option is not active, this setting is invalid.

Unhold (Default):

When the alarm is released, the output relay stays off.

Hold: The output relay stays on until an Alarm ACK operation is performed.

• Alarm Indicator

Select the alarm indicator when returning from an alarm to the normal state of

operation.

Unhold (Default):

The alarm display ends when the alarm is released.

Hold: The alarm display stays on until an Alarm ACK operation performed.