Control Functon Settngs

SP Tracking

Turn the target setpoint tracking ON or OFF.

PV Tracking

Turn the measurement value tracking ON or OFF.

Target Setpoint Limiter

Set the value in the measurement span EU (0.0 to 100.0%). L must be smaller than U.

Output Velocity Limiter

Select or clear the check box to turn the output velocity limiter ON or OFF, and specify a

value between 0.1 and 100.0. This is unavailable for style number S2 or later if you set

[Control Output] to [On/Off control] in the [Setup] tab for [Internal Loop].

Anti-reset Windup

Select the anti-reset windup from [Auto] or [Manual]. This is unavailable for style number

S2 if you set [Control Output] to [On/Off control] in the [Setup] tab for [Internal Loop].

Dev Band

Set the deviation band of the anti-reset windup between 50.0 and 200.0%.

This setting is only valid when the [Anti-reset Windup] is set to [Manual].

Control Groups

Set the groups to which control functions apply.

From the [Setting] tab, select [Control Group].

Group Name

Enter a group name using a maximum of 16 characters.

8.4 Control Functon General Settngs