Yokogawa Data Logging Software GA10 User Manual

Page 39

Advertising
background image

3-15

IM 04L65B01-01EN

Waveform Settings
Waveform settings are explained below.

(1) No.

These are waveform numbers assigned sequentially

starting with W01. You cannot change the numbers.

Click the boxes to specify whether to display the

waveform.

(2) Tag

Specify the tag to assign to the waveform. Clicking

a button displays a separate window. Select a tag

number to apply it to the sheet.

(3) Y-Axis

No.: Specify the Y-axis to use in the waveform

display.

Mode: Select Detail or Compact mode.

Type: Specify the type of scale to add to the Y-scale

of the waveform. Select Linear or Logarithmic.

Title: Type the Y-axis title of the waveform. Enter up

to 30 characters.

(4) Form.

Set the display format on the Monitor Page to fixed

point or floating point.

F: Fixed point display

E: Floating point display

(5) Meter

Specify the type of meter to display on the Meter

Monitor. Select bar meter

or analog meter

.

(6) Scale MIN and MAX

Type the minimum and maximum values of the scale

on the Monitor Page to define the display range.

(7) Scale Interval

Set whether to specify the Y-axis scale interval of

the waveform. Leave unselected to use the default

scale interval. To specify the scale interval, select

the check box and enter a value.

(8) Zone

MAX: Specify the maximum Y-axis position for

displaying the waveform.

MIN: Specify the minimum Y-axis position for

displaying the waveform.

This determines the waveform display position.

(9) Color

Specify the waveform display color. To change the

color, click the appropriate cell to display a separate

window. Select a color to apply it to the sheet.

(10) Trip

Use: Click to use the waveform trip line.

Value: Type the value.

Color: Specify the trip line color. To change the

color, click the appropriate cell to display a separate

window. Select a color to apply it to the sheet.

Chapter 3 Configuring and Starting Data Collection and Recording

Collectively Edit Setup Data
To collectively edit setup data, you must select the target

setup data and then click a button on the action bar,

which is at the bottom of the window. The result varies

depending on the type of icon you press on the action bar

(see the following table).

To select the range: The procedure is the same as

explained on

page 3-13

.

Type

Name

Result

Show or hide

Enable or disable

F-Type/E-Type

Switches the check box state between

selected and unselected.

Switches the item selection state.

If the data values in the selected range

are not all the same, clicking this icon will

switch all of them to match the first data

value in the selected range.

Increment

Assigns increasing tag index numbers

starting with the first tag in the selected

range.

Default

Resets the value to default.

Y-axis grouping

(unit)

Groups Y-axes whose unit is the same

together.

Y-axis grouping

(unit & scale)

Groups Y-axes whose unit and scale value

are the same together.

Copy

Copies the settings of the first tag in the

selected range to the other tags in the

selected range.

Copy flag

Switches between selected and

unselected states for items to be pasted

when copying setup data. The items are

normally selected (pasted).

Clicking this button causes the

corresponding column to become

unselected and will not be pasted to.

You can also copy and paste selected content using the

Edit

menu.

Assigning Tags Automatically
Tags assigned on the Tag Setting Page can be assigned

automatically to display groups.

There are two methods for automatic assignment.

• Assign According to Tag Number

When you specify the number of tags to assign to

each display group, the specified number of tags are

assigned in order from the first number of display

group 1 on the Tag Setting Page.

For example, if the total number of tags is 50 and

you set the number of tags to 10, 10 tags will be

assigned to each group from Group 1 to 5.

• Assign According to Device

The tags of a single device are assigned to each

display group. For each device (device number)

that a tag has been assigned to, assign the tag to

a display group. Tags are assigned in ascending

order by device number starting with display group

1. Within a display group, tags are assigned in

ascending order by tag number.

If the number of tags of a device is greater than the

number of waveforms in a display group, multiple

display groups will be used for the device.

Advertising