Yokogawa Data Logging Software GA10 User Manual

Page 46

Advertising
background image

3-22

IM 04L65B01-01EN

Recording Interval
Select the interval from the drop-down list.

Options: 100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, 20 s,

30 s, 1 min, 2 min, 5 min, 10 min

The intervals that are displayed in the list are integer

multiples of the collection period specified on the Monitor

Page. If Data time is set to Device time, you cannot

specify the record interval.
Record File Type
Specify the data output format.

You can save the recorded file in binary format (.dld

extension) or Excel format (.xlsx extension).
Start Condition
You can specify the following for the start condition.

Start Condition

Description

Immediate

Starts recording when the Start Recording button

is clicked.

Specified Time

Starts recording when the specified time arrives.

Specified Period Records at the specified period.

Alarm

Starts recording using the alarm status as a

trigger.

Level

Starts recording using a collected data value as

a trigger.

Stop Condition
You can specify the following for the stop condition.

Stop Condition

Description

Continuous

Stops recording when the Stop Recording button

is clicked.

Specified Time

Stops recording at the specified time. If the start

condition is set to Alarm or Level, GA10 enters a

recording standby state.

Specified

Duration

Stops recording when the specified time elapses

after recording starts. If the start condition is set to

Alarm or Level, GA10 enters a recording standby

state.

Data Number

Stops recording at the specified number of data

points. If the start condition is set to Alarm or

Level, GA10 enters a recording standby state.

Specified Period Stops recording at the specified period and enters

recording standby state.

Alarm

Stops recording using the alarm status as a

trigger and enters recording standby state.

Level

Stops recording using a collected data value as a

trigger and enters recording standby state.

Note

• If you set the start condition to Specified Period, the

stop condition is fixed to Specified Period.

• If the start condition is set to Specified Period and

the recording start time is set to the same time as the

record stop time, the recorded data file is not divided

at every interval.

• If the start condition is set to Specified Period and the

period is set to the 31st of every month, for months

that do not have 31 days, the date is automatically set

to the last day of the month.

• If you set the start condition to Specified Time,

you cannot specify a nonexistent time due to DST

(daylight saving time) transition.

• If the specified time overlaps due to the DST

transition, the first time is used to start recording.

Chapter 3 Configuring and Starting Data Collection and Recording

An example of the procedure when the start condition is

set to Alarm is explained below.

1

Set Start Condition to

Alarm.

The tag range, reference alarm, and alarm value are

displayed.

Alarm value

Tag range

Reference alarm

2

Click the first or last tag selection button.

A tag selection dialog box appears.

3

Select the applicable tag range.

The dialog box closes, and the tag selection button

display changes to the selected tag.

4

Select the reference alarm.

5

Set the alarm value to

Happen (alarm activated

state) or

Release (alarm released state).

Click the Start Recording button to enter the record-

ing standby state. When the monitored alarm reach-

es the specified alarm value, recording starts.

• If the stop condition is set to Alarm

The setting procedure is the same as described

above.

GA10 operates in the following manner.

If the start condition is set to Alarm or Level, when the

specified alarm value is reached during recording, GA10

stops recording and enters the recording standby state.

If the start condition is not set to Alarm or Level, when the

specified alarm value is reached during recording, GA10

stops recording.

An example of the procedure when the start condition is

set to Level is explained below.

1

Set Start Condition to

Level.

Tag range, threshold value, and operation direction

appear.

Operation direction

Type the threshold.

Tag range

2

Click the first or last tag selection button.

A tag selection dialog box appears.

3

Select the applicable tag range.

The dialog box closes, and the tag selection button

display changes to the selected tag.

4

Enter the threshold value.

5

Set the operation direction to Up (data value is
greater than or equal to the threshold) or Down
(data value is less than or equal to the threshold).

Click the Start Recording button to enter the record-

ing standby state. When the monitored tag value

reaches the threshold in the specified direction,

recording starts.