Power vented blowers troubleshooting guide – Sterling QVEB User Manual

Page 22

Advertising
background image

3. Defective fan switch.

4. Lack of power at unit.

1. Fan switch heater element improperly

wired.

2. Defective fan switch.
3. Motor overload protector cycling ON

and OFF.

4. Motor not properly oiled.

1. Improperly wired fan control.
2. Main burners not lighting while

thermostat calls for heat.

3. Defective fan switch.

1. Incorrect gas input.
2.

Heater

undersized.

3.

Thermostat

malfunction.

4. Heater cycling on limit control.

1.

Thermostat

malfunction.

2. Heater runs continuously.

a. Improper thermostat or transformer

wiring at gas valve.

b. Short circuit.

c. Defective or sticking gas valve.
d. Excessive gas supply pressure.

1. Fan switch heater element improperly

wired.

1. Incorrect manifold pressure or input.
2. Voltage to unit too high.

3. Air throughput too high.

1. Thermostat not calling for heat.
2. No low voltage.

3. Spark gap closed or too wide.
4. Broken or cracked ceramic on spark

electrode.

1. Loose S8600 connections.

2. Improper gas pressure.

3. Is spark in pilot gas stream?
4. No pilot gas — do not use match to

test - presence of gas is easily detected
by the odor.

3. Check for 24V across 1 and 3 terminals on fan

time delay switch. If 24V is present, jumper
terminals numbered 2 and 4. If motor runs, the
fan switch is defective and must be replaced. If
24V is not present, check wiring per diagrams.

4. Replace fuse or turn on power.

1. Be sure fan switch heater terminals

are connected per diagrams.

2. Replace fan switch.
3. Check motor amps against motor name

plate rating, check voltage, replace fan
motor if defective.

4. Refer to label on motor.

1. Check all wiring.
2. Refer to H or N symptoms.

3. Replace fan switch.

1.

Refer

to

“Operation”.

2. This is especially true when the heated

space is enlarged. Have the heat loss
calculated and compare to the heater output
(80% of input). Your gas supplier or installer
can furnish this information. If heater is
under sized, add additional heaters.

3.

Replace

thermostat.

4. Check air movement through heat

exchanger. Check voltage to fan
motor. Clean fan blade and heat
exchanger and oil fan motor.

1.

Replace

thermostat.

2.

a. Check wiring per diagrams.

b. Check operation at valve. Look for short

(such as staples piercing thermostat
wiring), and correct.

c. Replace gas valve.
d. Refer to “Operation”.

1. Be sure fan switch heater terminals are

connected per diagrams.

1.

Refer

to

“Operation”.

2. Check motor voltage with fan running.

Should be 115 volts AC.

3.

Refer

to

“Operation”.

1. Close thermostat contacts.
2. Check for 24V across 24V terminals of

S8600.

3. Set gap to 0.1".
4. Replace pilot assembly.

1. Check all connections, term. PV feeds 24V

to pilot valve.

2. Check pressure — pressure that is either

too high or too low may cause a problem.

3. Spark should arc from electrode.
4. Check pilot line for kinks. Ensure there

are no drafts.

O. continued

P. Fan motor turns on and off while

burner is operating.

Q. Fan motor will not stop.

R. Not enough heat.

S. Too much heat.

T. Cold air is delivered on start up.

U. Cold air is delivered during heater

operation.

V. No Spark.

W. Spark present but pilot does not

light.

22

Power Vented Blowers Troubleshooting Guide

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

Advertising