Sterling QVEB User Manual

Page 4

Advertising
background image

Unit

Size

100 125 150 175 200 225 250 300 350 400

PERFORMANCE DATA ‡

Input

BTU/Hr

100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000

(kW)

(29.3)

(36.6)

(43.9)

(51.2)

(58.6)

(65.9)

(73.2)

(87.8)

(102.5)

(117.1)

Output

BTU/Hr

80,000 100,000 120,000 140,000 160,000 180,000 200,000 240,000 280,000 320,000

(kW)

(23.4)

(29.3)

(35.1)

(41.0)

(46.9)

(52.7)

(58.6)

(70.3)

(82.0)

(93.7)

Thermal

Effi

ciency

(%)

80 80 80 80 80 80 80 80 80 80

Free

Air

Delivery

CFM

1,200 1,575 1,975 2,300 2,400 2,600 2,850 3,950 4,600 4,800

(cu. m/s)

(0.566)

(0.743)

(0.932)

(1.086)

(1.133)

(1.227)

(1.345)

(1.864)

(2.171)

(2.266)

Air

Temperature

Rise

F

Deg.

62 59 56 56 62 64 65 56 56 62

(C Deg.)

(34)

(33)

(31)

(31)

(34)

(36)

(36)

(31)

(31)

(34)

Outlet

Velocity

FPM

880 950 1,030

1,045 965 935 930 1,080

1,090 1,000

(m/s)

(4.47)

(4.83)

(5.23)

(5.31)

(4.90)

(4.75)

(4.72)

(5.49)

(5.54)

(5.08)

Full Load Amps at 115V

8.3

9.8

10.6

10.6

15.2

15.2

15.2

15.2

18.6

18.6

MOTOR DATA :

Motor

HP

1/4 1/3 1/2 1/2 3/4 3/4 3/4 3/4 1

1

Motor (kW)

(0.19)

(0.25)

(0.37)

(0.37)

(0.56)

(0.56)

(0.56)

(0.56)

(0.75)

(0.75)

Motor Type

SPH

SPH

SPH

SPH

SPH

SPH

SPH

SPH

cap.start

cap.start

R.P.M.

1,725

1,725

1,725

1,725

1,725

1,725

1,725

1,725

1,725

1,725

Amps @ 115V

5.1

6.6

7.4

7.4

12.0

12.0

12.0

12.0

15.4

15.4

DIMENSIONAL DATA in. (mm)

“A”

Height

to

Top

of

Unit

31-1/4 31-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4

(794) (794) (921) (921) (921) (921) (921) (921) (921) (921)

“B”

Width

of

Unit

17-7/8 20-5/8 20-5/8 23-3/8 26-1/8 28-7/8 31-5/8 37-1/8 42-5/8 48-1/8

(454) (524) (524) (594) (664) (733) (803) (943)

(1083) (1222)

“C”

Height

to

Top

of

Hanger

34-1/8 34-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8

(867) (867) (994) (994) (994) (994) (994) (994) (994) (994)

“D” Depth to Rear of Housing

42-5/8

44-1/4

44-1/4

47

47

51

51

48-1/4

51

51

(1083) (1124) (1124) (1194) (1194) (1295) (1295) (1226) (1295) (1295)

“E”

Hanging

Distance

Width 14-1/2 17-1/4 17-1/4 20 22-3/4 25-1/2 28-1/4 33-3/4 39-1/4 44-3/4

(368) (438) (438) (508) (578) (648) (718) (857) (997) (1137)

“F”

Discharge

Opening

Width 15-3/8 18-1/8 18-1/8 20-7/8 23-5/8 26-3/8 29-1/8 34-5/8 40-1/8 45-5/8

(391) (460) (460) (530) (600) (670) (740) (879)

(1019) (1159)

“J” to Centerline of Flue

5-7/8

7-1/4

7-1/4

8-5/8

10

11-1/4

12-3/4

15-1/2

18-1/4

21

(149) (184) (184) (219) (254) (286) (324) (394) (464) (533)

“L”

Hanger

Location

16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8 16-3/8

(416) (416) (416) (416) (416) (416) (416) (416) (416) (416)

“M”

Hanging

Distance

Depth 16-3/8 16-3/8 16-3/8 17-7/8 17-7/8 21-7/8 21-7/8 21-7/8 21-7/8 21-7/8

(416) (416) (416) (454) (454) (556) (556) (556) (556) (556)

Flue

Size

Dia-in.

*

4 4 4 4 5 5 5 6 6 6

(Dia-mm)

(102)

(102)

(102)

(102)

(127)

(127)

(127)

(152)

(152)

(152)

Blower

Size-in.

9 10 10 12 12 12 12 (2)

10

(2)

12

(2)

12

Gas

Inlet-Natural

Gas-in.

1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4

Gas

Inlet-LP

Gas-in.

1/2 1/2 1/2 1/2 1/2

1/2

OR

3/4

Approx.

Shipping

Wt.

lb.

262 279 314 336 363 408 427 471 561 594

(kg)

(119)

(127)

(142)

(152)

(165)

(185)

(194)

(214)

(254)

(269)

4

DIMENSIONS .XXX STANDARD UNITS
DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS

Figure 2 -
Unit
Dimensions

Table 1 – Performance and Dimensional Data – Power Vented Blower Unit Heater

‡ Ratings shown are for unit installations at elevations between 0 and 2000 ft. (610m). For installations in USA above 2000 ft. (610m), the unit input must be derated 4% for each 1000 ft. (305m) above

sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).

For installations in Canada, any references to deration at altitudes of 2000 ft. (610m) are to be ignored. At altitudes of 2000 to 4500 ft. (610 to 1372m), the unit must be derated to 90% of the normal

altitude rating, and be so marked in accordance with the ETL certifi cation.

LEGEND:
SPH = SPLIT PHASE
CAP. START = CAPACITOR START

Advertising