DIL Switch Settings – Programmable Features

Important:

Changes made to any DIL switch settings will only take effect after the Alert
Point has been reset using the master key switch.

Factory settings

Features

SW1

SW2

SW3

Tone Sound Pattern

OFF

OFF

OFF

1

800Hz - 970Hz (Sweep)

ON

OFF

OFF

2

800Hz - 970Hz (Sweep)

OFF

ON

OFF

3

988Hz / 250ms - 645Hz / 250ms (Alternating)

ON

ON

OFF

4

670Hz / 250ms - 845Hz / 370ms (Alternating)

OFF

OFF

ON

5

800Hz - 970Hz in 330ms (Sweep)

ON

OFF

ON

6

2400Hz - 2850Hz in 110ms (Sweep)

OFF

ON

ON

7

2400Hz - 2850Hz in 330ms (Sweep)

ON

ON

ON

8

Not Implemented

Action

External Power Provided -
(12-30V DC)

External power is to be supplied. NB: absence of power will indicate
fault (LED flashing red )
No external power is to be supplied. NB: absence of power will not
indicate a fault

Relay is only triggered on the activated unit in a network

Integral Sounder Alarm
Tone

SW4 ON

SW4 OFF

SW5 ON

DI L S w itch S etting

Unit's Relay activates in a network even if this unit was not triggered

External Sounders/Beacons are NOT triggered during `alarm'
condition

External Sounders/Beacons are triggered during `alarm' condition

Relay Mode

Disable External Sounders
& Strobes / Beacons

SW5 OFF

SW6 ON

SW6 OFF

Sounder Duration Timer

SW7 SW8

OFF OFF

ON OFF

OFF ON

ON ON

Sounder Duration

Sounders run continuously (until manually reset)

Sounders switch off automatically after 30 seconds

Sounders switch off automatically after 3 minutes

Sounders switch off automatically after 20 minutes

Strobe / Beacon Duration
Timer

SW9 SW10

Strobe / Beacon Duration

OFF OFF

Strobes / Beacons run continuously (until manually reset)

ON OFF

Strobes / Beacons switch off automatically after 30 seconds

OFF ON

Strobes / Beacons switch off automatically after 3 minutes

ON ON

Strobes / Beacons switch off automatically after 20 minutes

Auto Reset

SW11 ON

SW11 OFF

Alert Point returns to `standby' condition after resetting with the
reset key
Alert Point latches in 'alarm' condition until it is manually reset using
the master key switch
The Alert Point expects to be connected to another Alert Point,
otherwise a fault is indicated (LED flashing / constant red)
No fault will be indicated if an Alert Point is not connected to
another Alert Point, it is not looking for a connection

Networking the Alert Point

SW12 ON

SW12 OFF

- 19 -

Safety Technology International (Europe) Ltd.

Unit 49G • Pipers Road • Park Farm Industrial Estate

Redditch • Worcestershire • B98 0HU • England

Tel: +44 (0) 1527 520 999 Fax +44 (0) 1527 501 999

Email: [email protected] Web: www.sti-europe.com

Safety Technology International, Inc.

2306 Airport Road • Waterford • Michigan • 48327

Tel: 248 673 9898 Fax: 248 673 1246

Email: [email protected] Web: www.sti-usa.com

Alertpoint Installation rev 1_2 Sep10_webversion.