User manual – STI AP-1-G-I User Manual

Page 4

Advertising
background image

User Manual

Programmable Features

Settings

1. Integral Sounder Tones: DIL Switch No SW1 - SW3

The Alert Point has seven different
selectable alarm tones ranging from
95dB to 102dB, along with a prefixed
tamper tone.

2. External Power Provided (12-30V DC): DIL Switch No SW4

This setting allows the unit to be run from
an external power source.

3. Relay Setting: DIL Switch No SW5

When part of a network, this setting allows the option of sending a triggering signal
via the relay to an alarm panel, either:
• Relay is only triggered on the activated unit
• Relay sends triggering signal even when another unit is activated.

4. External Sounder/Strobe Trigger: DIL Switch No SW6

This setting allows the option of sending a triggering signal to externally fitted
sounders, along with strobes/beacons.

5. Internal & External Sounder Timer Options: DIL Switch No SW7 & SW8

4 alarm durations are available and can be selected by changing the DIL switch
settings. These are: continuous, 30 seconds, 3 minutes and 20 minutes.

If any duration period other than `continuous’ is used, the alarm will silence
after the selected time has elapsed.

The LED will continue to flash red

until the unit is reset using the reset key.

6. External Strobe Timer Options: DIL Switch No SW9 & SW10

4 strobe durations are available and can be selected by changing the DIL switch
settings. These are: continuous, 30 seconds, 3 minutes and 20 minutes.

If any duration period other than ‘continuous’ is used, the strobe will cease
flashing. The Alert Point will still need to be reset, the LED will still flash red until
this has been done.

7. Key Switch – Manual or Auto Reset: DIL Switch No SW11

This allows the user greater control if misuse becomes a major factor.
Auto reset: The Alert Point will fully reset after activation when using the reset key.
Manual: Even if the Alert Point is reset after activation using the reset key, all
sounders and strobes will continue to run until the unit is reset using the master key
switch.

8. Networking the Alert: DIL Switch No SW12

If this switch is `ON’ the Alert Point expects to be connected to another Alert Point
otherwise a fault is indicated.
If the switch is `OFF’ the Alert Point will not expect to be connected to another
Alert Point.

Note: DIL Switch settings are shown on page 19

PCB Layout

DIL Switch

- 8 -