STI AP-1-G-I User Manual

Page 6

Advertising
background image

- 11 -

Installing External Sounders

Step 1. Ensure that the unit is switched `OFF’.

Step 2. Insert the external sounder wires into the correct terminals.

Step 3. DIL switch SW6 – should be ‘OFF’ (external sounders/strobes to trigger during alarm

condition).

Important: Please ensure all sounders have their own power source and are wired correctly in

accordance with their own installation manuals.

Warning: Incorrectly installed external devices may cause irreversible damage to the Alert Point.

Step4. Turn the unit `ON’ using the master key switch.

Step 5. The LED will now flash green every 8 seconds (or will remain constant if connected to an

external power supply), indicating that the unit is functioning correctly.

Step 6. Test:

When the operating element is depressed, the unit will go into alarm condition: the externally

installed sounders should now sound.

Step 7. Reset the Alert Point using the reset key, all sounders should now silence.

Please note: If the `Auto Reset’ is disabled (DIL switch SW11 `OFF’) the sounders will continue

to sound until the master Key switch is turned `OFF’. When turned back `ON’ the unit

should be in `standby’ condition.

IMPORTANT: Enabling/Disabling external sounders will also enable/disable any strobes or

beacons also wired to this unit.

External Sounder +

External Sounder -

Diagram of PCB terminal layout

- 12 -

Installing External Strobes / Beacons

Step 1. Ensure that the unit is switched `OFF’.

Step 2. Insert the external strobe / beacon wires into the correct terminals.

Step 3. DIL switch SW6 – should be ‘OFF’ (external sounder(s)/strobes(s) to trigger during alarm

condition).

Important: Please ensure all external strobe(s)/beacon(s) have their own power source and are wired

correctly in accordance with their own installation manuals.

Warning: Incorrectly installed external devices may cause irreversible damage to the Alert Point.

Step 4. Turn the unit `ON’ using the master key switch.

Step 5. The LED will flash green every 8 seconds (or will remain constant if connected to an external

power supply), this indicates that the unit is functioning correctly.

Step 6. Test:

When the operating element is depressed, the unit will go into alarm condition: the externally

installed strobe(s)/beacon(s) should now flash.

Step 7. Reset the Alert Point using the reset key, all strobe(s)/beacon(s) should now cease flashing.

Please note: If the `Auto Reset’ is disabled (DIL switch SW11 ‘OFF’) the strobe(s)/beacon(s) will

continue to flash until the master key switch is turned `Off’. When turned back `On’ the unit

should be in `standby’ condition.

External Strobe / Beacon +

External Strobe / Beacon -

Optional Internal Beacon
An optional extra (

not supplied as standard

) for the Alert Point is the capacity to incorporate an

internal beacon – this can provide for those who may be audibly impaired.

Note:
All external sounders must be hard-wired
using 2-core cable, and must have their
own power supply.
It is recommended that external wiring
does not exceed 50 metres.

Advertising
This manual is related to the following products: