Environmental considerations

For successful installation and operation of the switch, ensure that the following environmental
requirements are met:

At a minimum, adequate cooling requires that you install the switch with the intake side, as
indicated by the airflow direction of the fan assemblies, facing the cool-air aisle.
The chassisshow output indicates “Reverse” for non-port side intake and “Forward” for port
side intake.

All equipment in the rack should force air in the same direction to avoid intake of exhaust air.

Airflow requirements outlined in

Table 5

must be met. Note that the requirements differ based

on the direction of the airflow.

The ambient air temperature does not exceed 40

°

C (104

°

F) while the switch is operating.

Table 5

lists the acceptable environmental ranges for both operating and nonoperating (such as

during transportation or storage) conditions.

Rack considerations

For successful installation and operation of the switch in a rack, ensure the following rack
requirements are met:

The rack must be a standard EIA rack.

A rack space that is two rack units (2U) high; 8.90 cm (3.50 inches) high and 48.3 cm (19
inches) wide.

There are three rack kit options that accommodate the Brocade 6520, a four-post fixed rack
kit, a two-post Telco rack kit, and a four-post sliding rail rack kit. See their respective
installation manuals for details.

TABLE 5

Environmental requirements

Condition

Acceptable during operation

Acceptable during non-operation

Ambient
temperature

0º to 40ºC (32º to 104ºF)

-25º to 70ºC (-13º to 158ºF)

Humidity

10% to 85% RH non-condensing, at
40ºC (104ºF)

10% to 90% RH non-condensing, at 70ºC
(158ºF)

Altitude

0 to 3 km (9,842 feet) above sea level

0 to 12 km (39,370 feet) above sea level

Shock

20 G, 6 ms, half-sine wave

33 G, 11 ms, half-sine wave, 3/eg Axis

Vibration

0.5 G sine, 0.4 gms random, 5-500 Hz

2.0 G sine, 1.1 gms random, 5-500 Hz

Air flow

Port side exhaust -

Maximum - 176.7 cmh (104 cfm)
Nominal - 52.7 cmh (31 cfm)

Port side intake -

Maximum - 185.2 cmh (109 cfm)
Nominal - 56.1 cmh (33 cfm)

N/A

Heat dissipation

1378.5 BTU/hr (no optics configuration)
1706.1 BTU/hr (fully populated port
configuration)

N/A