Removal and replacement of power supplies and fans, In this chapter, Removal and replacement introduction – Brocade 6520 Hardware Reference Manual User Manual

Page 39: Before beginning replacement, Chapter 4

Advertising
background image

Brocade 6520 Hardware Reference Manual

27

53-1002705-02

Chapter

4

Removal and Replacement of Power Supplies and Fans

In this chapter

Removal and replacement introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Power supply removal and replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Fan removal and replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

SFP+ transceiver removal and replacement . . . . . . . . . . . . . . . . . . . . . . . . . 35

Removal and replacement introduction

NOTE

Read the

“Installation and safety considerations”

before servicing.

The field-replaceable units (FRUs) in the Brocade 6520 can be removed and replaced without
special tools. The Brocade 6520 can continue operating during the FRU replacement if the
conditions specified in the procedures are followed.

DANGER

The procedures in this manual are for qualified service personnel.

Before beginning replacement

CAUTION

This document describes how to change field-replaceable units (FRUs) for units with either a
port-side air exhaust or a port-side air intake. You must replace a failed unit with the same type of
unit.
This applies to both power supplies and fans.
A new FRU must have the same part number (P/N) as the FRU being replaced. The
manufacturing P/N is located on the top of the FRU.

You can use external labels as a guide. Refer to

Figure 8

. Both the power supply and fan FRUs are

labeled with an airflow symbol on the faceplate to indicate whether the assembly takes in or
exhausts air. The label also appears on the top of the assembly.

ATTENTION

All fans and power supplies must have the same airflow symbol (E or I) to be compatible with each
other.