System power specifications – Brocade 6505 Hardware Reference Manual User Manual

Page 46

Advertising
background image

Facility requirements

TABLE 6

Type

Requirements

Electrical

• Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on

the switch nameplate.

• Circuit protected by a circuit breaker and grounded in accordance with local electrical

codes.

Refer to

System power specifications

on page 46 for complete power supply specifications.

Thermal

• A minimum airflow of 79.8 cubic meters/hour (47 cubic ft/min.) available in the immediate

vicinity of the switch.

• Ambient air temperature not exceeding 40 ° C (104 ° F) while the switch is operating.

Rack (when rack-
mounted)

• One rack unit (1U) in a 48.3 cm (19-inch) rack.
• All equipment in rack grounded through a reliable branch circuit connection.
• Additional weight of switch not to exceed the rack’s weight limits.
• Rack secured to ensure stability in case of unexpected movement.

System power specifications

The power supplies are universal and capable of functioning worldwide without voltage jumpers or
switches. They meet IEC 61000-4-5 surge voltage requirements and are autoranging in terms of
accommodating input voltages and line frequencies. Each power supply has built-in fans for cooling.

The following table lists the system power specifications for the Brocade 6505.

System power specifications

TABLE 7

Specification

Value

Maximum output (per power supply)

150 watts, 12 VDC

AC input power draw

Idle, no optics: 60 W

Maximum, fully populated with 16 Gbps SWL optics: 80 W

AC input voltage

85-264 VAC, nominal 100-240 VAC

AC input line frequency

47-63 Hz, nominal 50-60 Hz

AC inrush current

Maximum of 35A @ 240 VAC for 10 ms or less

Input line protection

AC lines are fused.

System power specifications

46

Brocade 6505 Hardware Reference Manual

53-1002449-04