3 phase, 3 phase 1 phase, Il0102 – Star Water Systems CJ101 (Flint & Walling) User Manual

Page 4: Electrical

Advertising
background image

6

95 North Oak Street • Kendallville, IN 46755 • Copyright © 2012. All rights reserved.

7

95 North Oak Street • Kendallville, IN 46755 • Copyright © 2012. All rights reserved.

ELECTRICAL

Hazardous voltage.

Can shock, burn

or cause death.

Failure to follow

warnings can

cause fatal or

severe shock

hazard or

equipment failure.

Ground motor before connecting

to electrical power supply.

Connect the motor frame to

equipment grounding conductor by
using green screw. Do not connect
green ground wire to any of the motor
leads.

Do not ground to a gas supply

line.

Turn off power to motor before working on electrical

connections.

Supply voltage must be within ±10% of nameplate

voltage. If in doubt consult a licensed electrician.

Use wire size specified in wiring Chart E. If possible,

connect pump to a separate branch circuit with no other
appliances on it. If wiring diagram on motor model plate
differs from diagram shown in figures 8, 9 & 10, follow
diagram on motor.
All wiring should be performed by a qualified electrician
and in accordance with the national and local electric
codes.

WIRING
1. Motor voltages will vary depending upon the

motor horsepower and phase. Refer to the
motor nameplate and the Motor Data Chart
(Chart C) for voltage and electrical data.

Make certain that the power supply

conforms to the electrical specifications of the motor
supplied. Failure to do so may cause premature motor
failure and will void the warranty.

2. To change voltage, remove the rear access

cover, which is held in place with two (2)
screws. For proper electrical connection, refer
to the connection diagram located on the motor
nameplate or figures 8, 9, 10, 11 & 12.

Replace rear access cover before

starting or operating pump. Failure to do so can result
in personal injury.

MOTOR PROTECTION
1. All single phase motors have built in thermal

protection for all voltages. The overload
protects the motor against burnout from
overload of low voltage, high voltage and other
causes. The device is automatic and resets
itself once the temperature has dropped to
a safe point. Frequent tripping of the device

indicates trouble in the motor or power lines
and immediate attention is needed.

Never examine, make wiring changes

or touch the motor before disconnecting the main
electrical supply switch. The thermal device may have
opened the electrical circuit.

2. Three phase motors do not have a built in

thermal protection. It is recommended that a
properly sized magnetic or manual starter (both
with properly sized heaters) be used with all
three phase motors. Install starters following
instructions of the starter manufacturer. See
Figure 13 for magnetic starter wiring diagram.

3. All motors (single and three phase) should be

equipped with a correctly fused disconnect
switch to provide protection. consult local
or national electric codes for proper fuse
protection based on motor data chart (see
Charts C & E).

L1

L2

A

B

L1

L2

A

B

IL0180

YELLOW

115 VOLT

SINGLE PHASE

LINE

230 VOLT

SINGLE PHASE

LINE

WHITE

GRAY

RED

TAN

YELLOW

WHITE

GRAY

RED

TAN

Figure 8 - Wiring Diagram for Single Phase

1/3-2 HP

4

5

6

7

8

9

1

2

3

4

5

6

7

8

9

1

2

3

L1

L3

L2

L1

L3

L2

3-

ø

IL0770

LOW VOLTAGE 230V

HIGH VOLTAGE 460 V

Figure 9 - Wiring Diagram for Three Phase

Figure 13 - Magnetic Starter Wiring Diagram Three Phase

IL0102

Pressure
Switch

Fused
Disconnect
Switch

Lightning
Arrestor

Motor

#10 or Heavier Copper Ground Wire, Connect

to 10 Ft. Ground Rod or Well Casing

T1

T3

T2

T1

T2

X2

T3

02

03

L2

M

V

W

L3

L1

IL1229

6

5

4

3

2

1

7

8

9

6

5

4

7

8

9

3

2

1

HIGH VOLTAGE

LOW VOLTAGE

LINE

LINE

3 Phase

Figure 10 - Wiring Diagram for Baldor TEFC 3 Phase

motors

IL1231

T6

T5

T4

T3

T2

T1

T7

T8

T9

T6

T5

T4

T7

T8

T9

T3

T2

T1

T2

T5

T8

T6

T3

T7 T1

HIGH VOLTAGE

LOW VOLTAGE

GROUND

(WHEN REQ)

LINE

LINE

3 Phase

Figure 12 - Wiring Diagram for Marathon TEFC 3 Phase

motors

6

5

4

3

2

1

7

8

9

6

5

4

7

8

9

3

2

1

(4)

(10)

(9)

(3)

(2)

(4)

(10)

(9)

(3)
(2)

IL1230

HIGH VOLTAGE

LOW VOLTAGE

HIGH VOLTAGE

LOW VOLTAGE

LINE

LINE

BROWN

LINE

VIOLET

BLACK

YELLOW

BLUE

BROWN

LINE

VIOLET

BLACK

YELLOW

BLUE

3 Phase

1 Phase

Figure 11 - Wiring Diagram for Franklin Electric TEFC 1

Phase and 3 Phase motors