Wiring and Connecting

4. Installation

ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01

25

EIA-485 Circuit

Connect the EIA-485 annunciator circuit wiring to the removable terminal
blocks as illustrated below.

• Do not “T-Tap” the power-limited EIA-485 circuit. It will not function

properly.

• Leave the 120-ohm ELR (PN 71244) installed across the EIA-485

‘Out’ terminals at the last annunciator on the circuit. Remove this
resistor from all other annunciators.

• There is a maximum distance of 6000 feet between the panel and the

last annunciator on the EIA-485 circuit.

Figure 5 Connecting EIA-485 Wiring to Terminal Blocks

-

-

+

+

-

-

+

+

– +

-

-

+

+

A

C

S

_

ei

a.cdr

In
Out
Out
In

In
Out
Out
In

In
Out
Out
In

TB2 - Last
Annunciator

TB2 - Middle
Annunciator

TB2 - First
Annunciator

EIA-485 Circuit

from Control Panel