Providing power to annunciators – Fire-Lite ACM-32AF Annunciator Modules User Manual

Page 49

Advertising
background image

Providing Power to Annunciators

Appendix B: Sensiscan 2000

ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01

49

Providing Power to Annunciators

Sensiscan 2000 panels use the MPS-24AF or the MPS-24BF Main Power
Supply. This 24 VDC output is filtered, regulated, power-limited, and non-
resettable.

MPS-24AF - 3 A maximum current draw

MPS-24BF - 200 mA maximum current draw

The power run to the annunciator does not require a Power Supervision Relay
because loss of power is inherently supervised through a communications
loss.

Note: When not using the trouble input on annunciator or expander, jumper Trouble
Input terminals of TB1 on annunciator together.

MPS-24AF Main Power Supply - Connect the power run for the
annunciator module to the MPS-24AF TB3 Terminals 3(+) & 4(–), as shown
below.

Figure 21 MPS-24AF Power Connections - Sensiscan 2000

MPS-24BF Main Power Supply - Connect the power run for the
annunciator module to the MPS-24BF TB2 Terminals 3(+) & 4(–)as shown
below.

Figure 22 MPS-24BF Power Connections - Sensiscan 2000

T B 2

+ 24 R C O M M O N + 24 COMM ON

P O W E R L IM IT E D

B AT + B AT -

A

C

S

f-m

ps24a

.cdr

(–) Common

(+) 24 VDC Non-
Resettable Power

TB1

MPS-24AF Terminal Blocks

T B 3

T B 2

BAT T –

BAT T +

C O M M O N

C O M M O N

1 2 3 4

1 2

A

C

S

f-

m

ps24

b.cdr

(–) Common

(+) 24 VDC Non-Resettable Power

TB1

MPS-24BF Terminal Blocks