Appendix D: MS-9600

Providing Power to Annunciators

58

ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01

The EIA-485 circuit is connected between the ACS EIA-485 connector
(TB6) on the main circuit board to terminal TB2 on the annunciator (see
Figure 5 on page 25).

Figure 26 EIA-485 Circuit Connections - MS-9600

Providing Power to Annunciators

The MS-9600’s 24 VDC main power supply is contained on its main circuit
board. No more than 3 Amps current can be drawn from these terminals in
standby or alarm. This 24 VDC output is filtered, regulated, power-limited,
and non-resettable.

The power run to the annunciator need not require a Power Supervision Relay
because loss of power is inherently supervised through a communication
loss.

Note: When not using the trouble input on annunciator or expander, jumper Trouble
Input terminals of TB1 on annunciator together.

The power circuit is connected between terminal TB3 on the MS-9600 and
terminal TB1 on the annunciator (see Figure 6 on page 26) as shown below.

Figure 27 Power Supply Connections - MS-9600

+ –

T B 6

A

C

S

f-9

600.cd

r

TB2

TB6 - ACS EIA-485
connector

+ –

T B 3

A

C

S

f-9

600pw

r.

cdr

TB1

TB3 - Power Supply
Terminal Blocks

(+) 24 VDC Non-
Resettable Power

(–) Common