Program Mapping

Appendix B: Sensiscan 2000

ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01

51

Program Mapping

Annunciator points “track” or follow those system points they are
programmed to annunciate; they do not latch. The table outlines the
annunciation of various system circuits and functions.

Note: Control Switches marked “not used” will still function as local LAMP TEST or
local ACKNOWLEDGE switches for their respective points.

Table 5 Annunciator Program Mapping - Sensiscan 2000

Circuit Type

ACM-16ATF & AEM-16ATF

ACM-32AF

AEM-32AF

Red LED

Yellow LED

Control Switch

1

IZM-8F circuit

Indicates alarm status of

circuit

2

Indicates trouble
status of circuit

Not used

ICM-4F, ICE-4F
circuit

Indicates Activation

3

Indicates trouble
status of circuit

Controls Notification

Circuit

4

CRM-4F, CRE-
4F circuit

Indicates Activation

3

Indicates trouble
status of relay

Controls Relays

4

TCM-2F, TCM-
4F, VCM-4F,
DCM-4F circuit

Indicates Activation

3

Indicates trouble
status of relay

Remote Switch

Functions

4

Annunciator

Point #1

5

Indicates System Alarm

Indicates System
Trouble

ACKNOWLEDGE

Annunciator
Point #2

Not used

Indicates that signals
have been silenced

SIGNAL SILENCE

Annunciator
Point #3

Not used

Not used

SYSTEM RESET

Annunciator
Point #4

Not used

Indicates Supervisory
condition

Not used

Annunciator
Point #5

Indicates that
Notification Circuit #1
has been activated

Indicates trouble
status of circuit

Controls Notification
Circuit #1

Annunciator
Point #6

Indicates that
Notification Circuit #2
has been activated

Indicates trouble
status of circuit

Controls Notification
Circuit #2

Annunciator
Point #7

Indicates that Remote
Signaling Municipal Tie
has been activated

Indicates trouble

status of circuit

6

Controls Remote
Signaling Municipal
Tie

Annunciator
Point #8

Indicates that Alarm
Relay has been activated

Indicates AC fail
module/panel trouble

Controls Alarm Relay

1. These control switches are active only if: DIP Switch #5 (Receive Only) is ‘OFF’ and DIP Switch #7

(Switch Inhibit) is ‘OFF’.

2. With Software P/N #S500R4.0 or higher installed in the Sensiscan 2000, the manner in which the

IZM-8F circuits programmed as supervisory are annunciated depends upon whether Mode 1 or Mode
2 is selected.

3. These status LEDs are active only when the system is programmed for “Output Status”.
4. These control switches require that the system be programmed for “Output Control”.
5. If the Eight-Point Shift (DIP switch # 4) is set “ON,” the eight CPU functions will be shifted from

annunciator points 1 through 8 to points 57 through 64 (provided those points exist in the system).

6. Annunciator Point #7 yellow LED indicates Municipal Tie trouble if no UDACT-F is installed. It will

annunciate Low Battery/Ground Fault if a UDACT-F is installed in the system.