AEM-32AF

5. LED and Switch Functions

ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01

41

AEM-32AF

The following is a description of the LEDs and the switch located on the
AEM-32AF.

Figure 17 AEM-32AF LED & Switch Locations

Lamp Test Switch - When pressed, it lights all the LEDs (except the On-
line LED) on the expander module and sounds the piezo for as long as the
switch is held down.

Inactive LEDs - These two LEDs are not functional on expander modules.

Point-Active LED - Flashes to indicate an active point; after being
acknowledged it glows until reset.

Note: Loss of communication with the control panel is monitored & reported by the
ACM-32AF. If connection between ACM-32AF & AEM-32AF fails, the ACM-32AF will
show a trouble condition and the main control panel will show annunciator-point
trouble.

UDACT-F and Annunciators

The use of a UDACT-F (Universal Digital Alarm Communicator/
Transmitter) and an annunciator module on the same control panel will alter
the assignments of the trouble LEDs on annunciator points 3, 4, 5, 6, 7, and
8. Refer to the UDACT-F installation manual and the literature for the
respective fire alarm control panel for further details.