3 installing the ecc-fft, 1 operating power, 2 dip switch settings on ecc-fft – Fire-Lite ECC-FFT Firefighters Telephone User Manual

Page 13: Dip switch, Installing the ecc-fft

Advertising
background image

ECC-FFT Instruction Manual — P/N LS10031-000FL-E:B 9/4/2013

13

Installing the ECC-FFT

Installation

2.3 Installing the ECC-FFT

2.3.1 Operating Power

Connect the ECC-FFT to the appropriate DC power source. See Section 1.3 for compatible equip-
ment and Section 1.5 for power requirements.

2.3.2 DIP switch settings on ECC-FFT

Use the on-board DIP switch to assign the configuration setting to the ECC-FFT.

1. Refer to Figure 2.3 for location of the DIP switches on the ECC-FFT board.
2. Configure the ECC-FFT using the dip switch settings in Table 2.1. Add SLC modules to the

system through Autoprogram feature. See Section 3.3 for Autoprogram Operation.

DIP Switch

DIP Switch

ON

OFF

1

SLC Devices Installed

SLC Devices not Installed

2

Trouble Piezo Enabled

Trouble Piezo Disabled

3

SLC Class A Supervision

SLC Class B Supervision

4

Phone Circuit Class A Supervision

Phone Circuit Class B Supervision

5

Not Used

Leave in OFF position

6

Not Used

Leave in OFF position

Table 2.1 ECC-FFT DIP Switch Configurations

Figure 2.3 DIP Switch