6

ECC-FFT Instruction Manual — P/N LS10031-000FL-E:B 9/4/2013

This control panel has been designed to comply with standards set forth by the following regulatory agencies:

Underwriters Laboratories/Underwriters Laboratories Canada

National Fire Protection Association

NFPA Standards
This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code
Note: Audible signal appliances used in public mode applications, are required to have

minimum sound levels of 75 dBA at 10 feet (3 meters) and a maximum level of 120 dBA at the
minimum hearing distance from the audible appliance.
To ensure that the appliance is clearly heard, the audible appliance sound level must be at least

15 dBA above the average ambient sound level or 5 dBA above the maximum sound level with

a duration of at least 60 seconds, depending on which level is greater, with the sound level
being measured 5 feet (1.5 meters) above the floor.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 464 Audible Signaling Appliances
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1480 Speakers for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1711 Amplifiers for Fire Protective Signaling Systems
UL 1971 Signaling Devices for Hearing Impaired
UL 2572 Communication and Control Units for Mass Notification Systems
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
UFC Unified Facilities Criteria UFC 4-021-01: Mass Notification Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document

Document #15384

ECC-50/100 Manual

Document #LS10001-000FL-E

ECC-50/125DA Manual

Document #LS10027-000FL-E

MS-9200UDLS Series Manual

Document #52750

MS-9600(UD)LS Technical Manual

Document #52646

FCPS-24FS6/8 Field Charger/Power Supply

Document #51883

HP300ULX Power Supply

Document # 52386

This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).