ECC-FFT Instruction Manual — P/N LS10031-000FL-E:B 9/4/2013

Installation

UL Power-limited Wiring Requirements

2.4 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-lim-
ited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through dif-
ferent knockouts and/or conduits. A typical wiring diagram for the ECC-FFT is shown below.

Figure 2.4 UL Power-Limited Wiring Requirements

back view of dress panel

Note: The dress panel is shown swung
open for illustration purposes only.

Nonpower-
limited
circuit

Power-limited
circuits