SLC Device Installation

Installation

2.7 SLC Device Installation

2.7.1 List of SLC Devices

The following SLC device can be used with the Fire Fighters Phone. See the device installation
instructions for more information (packaged with the device). Refer also to the SLC Wiring Man-
ual #51309for more information.

2.7.2 Maximum Number of Devices

The ECC-FFT supports up to 24 MMF-301 devices on one FFT system.

2.7.3 Wiring Requirements for SLC Device

The following information applies to the MMF-301 - Mini Monitor module.

Wiring SLC in Style 4 (Class B) Configuration

No special wire is required for the ECC-FFT SLC loop. The wire can be untwisted, unshielded,
solid or stranded as long as it meets the National Electric Code 760-51 requirements for power lim-
ited fire protective signaling cables. Wire distances are computed using copper wire.

Maximum wiring resistance is 40 ohms to the farthest SLC device.

Maximum loop length depends on the wire gauge.

!

WARNING: RISK OF EQUIPMENT DAMAGE AND PERSONAL INJURY
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS UNIT. ALWAYS
DISCONNECT ALL SOURCES OF POWER BEFORE INSTALLING OR SERVICING.

Part Number

Model Name/Description

Install Sheet PN

MMF-301

Mini Monitor Module

I56-3654

I300

Fault Isolator Module

I56-1381

Wire Gauge

Max. Distance

22 AWG

1200 feet

18 AWG

3100 feet

16 AWG

4900 feet

14 AWG

7900 feet

12 AWG

10,000 feet